Figures and Tables
Figure 1. Joist configuration.
Figure 2. Joist prestressing tendon profile.
Figure 3. HJ-3 and HJ-4 web reinforcement.
Figure 5. High-performance concrete strength versus time.
Figure 6. Prestressing tendon stress versus strain.
Figure 7. Prestressing and casting of hybrid joists.
Figure 8. Completed hybrid joist construction.
Figure 10. Gap in FRP upgrade of HJ-3.
Figure 11. Epoxy injection of voids.
Figure 12. Internal strain gage layout for HJ-3, HJ-4, HJ-6, and HJ-7.
Figure 13. External strain gage layout on HJ-3.
Figure 14. External strain gage layout on HJ-4.
Figure 15. LVDT locations on test specimens.
Figure 16. Potentiometer locations on test specimens.
Figure 17. Block diagram of data recording system.
Figure 19. Load versus deflection for HJ-3, HJ-4, HJ-6, and HJ-7.
Figure 20. Load versus deflection cycles for HJ-4.
Figure 21. Deflected shape for HJ-3.
Figure 22. Deflected shape for HJ-4 before repair (top) and after FRP repair (bottom).
Figure 23. Deflected shape of HJ-6.
Figure 24. Deflected shape for HJ-7.
Figure 25. Strain distribution for HJ-3.
Figure 26. Strain distribution for HJ-4.
Figure 27. Strain distribution for HJ-6.
Figure 28. Strain distribution for HJ-7.
Figure 29. Strain distribution along strand length of HJ-3.
Figure 30. Strain distribution along strand length of HJ-4.
Figure 31. Strain distribution along strand length of HJ-6.
Figure 32. Strain distribution along strand length of HJ-7.
Figure 33. HJ-3 upgrade FRP strains.
Figure 34. HJ-4 repair FRP strains.
Figure 35. Crack patterns for HJ-6.
Figure 37. Crack patterns for HJ-7.
Figure 38. Crack patterns for HJ-3.
Figure 40. Crack Patterns of HJ-4 prior to FRP repair.
Figure 41. Crack patterns for HJ-4.
Figure 42. Shear repair design procedure.
Figure 43. Simply supported beam.
Joist Designation |
Configuration |
Web Shear Reinforcement |
Slab Width (ft) |
HJ-3 |
Upgraded with FRP |
Figure 4.6 |
6 |
HJ-4 |
Tested, then repaired with FRP |
Figure 4.6 |
6 |
HJ-6 |
Insufficient shear reinforcement |
Figure 4.8 |
4 |
HJ-7 |
Proper shear reinforcement |
Figure 4.8 |
4 |
Table 2. Epoxy Material Properties
Property |
Average |
Minimum |
Test Method |
-Tg @ 45% RH |
120OF |
100OF |
|
-Tg @ 95% RH |
110OF |
95OF |
|
-Tg 140OF Postcure (24 Hours) |
180OF |
140OF |
|
Tensile Strength |
10,100 psi |
9,500 psi |
ASTM D 638 Type 1 |
Tensile Modulus |
461,000 psi |
425000 psi |
ASTM D 638 Type 1 |
Elongation Percent |
5.00% |
3.50% |
ASTM D 638 Type 1 |
Flexural Strength |
11,500 psi |
10,500 psi |
ASTM D 790 |
Flexural Modulus |
400,000 psi |
375,000 psi |
ASTM D 790 |
Curing Schedule 72 hours post cure at 140OF
Property |
E-glass |
Polyaramid |
Test Method |
Yield/Denier |
1200 and 250 ypp |
2160 denier |
|
Density (g/cc) |
2.54 |
1.44 |
ASTM D 792 |
Tensile Strength (psi) |
440,000 |
400,000 |
SIM 13* |
Tensile Modulus (psi) |
10,500,000 |
17,000,000 |
STM 13 |
Elongation (%) |
4.2 |
2.5 |
STM 13 |
* Seguin Test Method - Hexel Manufacturing facility standard methods based on appropriate Standardized testing procedure
Property |
Average Value |
Minimum Value |
Test Method |
Areal Weight (oz/sq. yd.) |
27.2 |
24.4 |
STM 18 |
Tensile Strength dry 1" strip (Break Load lb.) |
1800 |
1600 |
STM 27 |
Air Permeability (cu. ft./min.) |
22 |
20 |
STM 26 |
Table 5. Composite Laminate Specification
Property |
Value |
ASTM Method |
Ultimate Tensile Strength min. (primary fiber direction)* |
65,000 psi |
D 3039 |
Elongation at break, min. |
2.00% |
D 3039 |
Tensile Modulus |
3.0 x 106 psi |
|
Ultimate Tensile Strength min. (90 degrees to primary fiber direction) |
4,800 psi |
D 3039 |
* Tensile retained 7 days @ 100% RH, 1,000 hours ozone, 1,000 hours alkali, 1,000 hours salt water, and 1,000 hours at 140OF
Cured for 48 hours at 140oF Using Hexcel Sample Preparation
Table 6. Composite Material Properties
Property |
Value |
Test Method |
Tensile Strength at 0o (ksi) |
65 |
ASTM D3039 |
Tensile Strength at 90o (ksi) |
6.0 |
ASTM D3039 |
Elastic Modulus (ksi) |
3,250 |
|
Ultimate Strain |
0.02 |
ASTM D3039 |
Coefficient of Thermal Expansion |
4.3 x 10-6 |
Table 7. Casting and Release Dates for Each Hybrid Joist Web
Specimen |
Casting Date |
Release Date |
HJ-3 |
1/29/96 |
2/5/96 |
HJ-4 |
1/29/96 |
2/5/96 |
HJ-6 |
2/12/96 |
2/16/96 |
HJ-7 |
6/20/96 |
6/24/96 |
Table 8. Instrumentation for HJ-3 Upgraded With FRP
Hybrid Joist Test |
HJ-3 |
Date: |
August 12, 1996 |
||||||||||||
USA Construction Engineering Research Laboratories |
Champaign, IL |
||||||||||||||
CERL |
CIR |
Conversion |
Location |
Location |
Gage |
||||||||||
Instrument |
Name/ |
Name |
Factor |
(X - Dir.) |
(Y - Dir.) |
Length |
Comments |
||||||||
Cable # |
(per volt) |
(in.) |
(in.) |
(in.) |
|||||||||||
Cell_N |
N / A |
5.000 kips |
141.000 |
N / A |
N / A |
Concentrated Load - 50 Kip Actuator | |||||||||
Stroke_N |
N / A |
0.300 inches |
141.000 |
N / A |
N / A |
||||||||||
Cell_S |
N / A |
5.000 kips |
250.000 |
N / A |
N / A |
Concentrated Load - 50 Kip Actuator | |||||||||
Stroke_S |
N / A |
0.300 inches |
250.000 |
N / A |
N / A |
||||||||||
POT_N |
P1 |
N / A |
1.994 inches |
141.000 |
N / A |
N / A |
Third span Deflection - Potentiometer | ||||||||
POT_Mid |
P2 |
N / A |
1.996 inches |
192.000 |
N / A |
N / A |
Midspan Deflection - Potentiometer | ||||||||
POT_S |
P3 |
N / A |
2.000 inches |
278.000 |
N / A |
N / A |
Quarter span Deflection - Potentiometer | ||||||||
Int_1 |
IS1 / 3 |
s19 |
0.00150 in/in |
40.000 |
N / A |
N / A |
Placed by the CIR |
||||||||
Int_2 |
IS2 / 2 |
s20 |
0.00150 in/in |
40.000 |
N / A |
N / A |
Placed by the CIR |
||||||||
Int_3 |
IS3 / 1 |
s21 |
0.00150 in/in |
40.000 |
N / A |
N / A |
Placed by the CIR |
||||||||
Int_4 |
IS4 / 12 |
s28 |
0.00150 in/in |
141.000 |
N / A |
N / A |
Placed by the CIR |
||||||||
Int_5 |
IS5 / 11 |
s26 |
0.00150 in/in |
119.000 |
N / A |
N / A |
Placed by the CIR |
||||||||
Int_6 |
IS6 / 10 |
s30 |
0.00150 in/in |
141.000 |
N / A |
N / A |
Placed by the CIR |
||||||||
Int_7 |
IS7 / 15 |
s31 |
0.00150 in/in |
163.000 |
N / A |
N / A |
Placed by the CIR |
||||||||
Int_8 |
IS8 / 14 |
s27 |
0.00150 in/in |
119.000 |
N / A |
N / A |
Placed by the CIR |
||||||||
Int_9 |
IS9 / 13 |
s33 |
0.00150 in/in |
163.000 |
N / A |
N / A |
Placed by the CIR |
||||||||
Int_10 |
IS10 / 18 |
s34 |
0.00150 in/in |
192.000 |
N / A |
N / A |
Placed by the CIR |
||||||||
Int_11 |
IS11 / 17 |
s35 |
0.00150 in/in |
192.000 |
N / A |
N / A |
Placed by the CIR |
||||||||
Int_12 |
IS12 / 16 |
s36 |
0.00150 in/in |
192.000 |
N / A |
N / A |
Placed by the CIR |
||||||||
LVDT_1 |
D1 |
N / A |
0.00500 in. |
75.500 |
1.000 |
7.205 |
Measured from the Top of the Slab | ||||||||
LVDT_2 |
D2 |
N / A |
0.00500 in. |
74.000 |
3.000 |
6.417 |
Measured from the Bottom Face of the Slab | ||||||||
LVDT_3 |
D3 |
N / A |
0.00500 in. |
73.000 |
12.250 |
4.134 |
Measured from the Bottom Face of the Slab | ||||||||
LVDT_4 |
D4 |
N / A |
0.00500 in. |
145.000 |
1.000 |
6.220 |
Measured from the Top of the Slab | ||||||||
LVDT_5 |
D5 |
N / A |
0.00500 in. |
143.000 |
3.500 |
7.480 |
Measured from the Bottom Face of the Slab | ||||||||
LVDT_6 |
D6 |
N / A |
0.00500 in. |
142.500 |
11.000 |
2.677 |
Measured from the Bottom Face of the Slab | ||||||||
LVDT_7 |
D7 |
N / A |
0.00500 in. |
142.000 |
22.750 |
2.756 |
Measured from the Bottom Face of the Slab | ||||||||
LVDT_8 |
D8 |
N / A |
0.00500 in. |
170.500 |
1.000 |
7.520 |
Measured from the Top of the Slab | ||||||||
LVDT_9 |
D9 |
N / A |
0.00500 in. |
N / A |
N / A |
N / A |
Not used for this test, Sensor moved to D7 | ||||||||
LVDT_10 |
D10 |
N / A |
0.00500 in. |
169.250 |
22.750 |
5.630 |
Measured from the Bottom Face of the Slab | ||||||||
LVDT_11 |
D11 |
N / A |
0.00500 in. |
193.500 |
1.000 |
5.276 |
Measured from the Top of the Slab | ||||||||
LVDT_12 |
D12 |
N / A |
0.00500 in. |
194.000 |
3.000 |
5.433 |
Measured from the Bottom Face of the Slab | ||||||||
LVDT_13 |
D13 |
N / A |
0.00500 in. |
194.000 |
22.500 |
5.039 |
Measured from the Bottom Face of the Slab | ||||||||
LVDT_14 |
D14 |
N / A |
0.00500 in. |
193.500 |
N / A |
5.197 |
Placed on top of Slab |
||||||||
LVDT_15 |
D15 |
N / A |
0.00500 in. |
243.000 |
N / A |
2.677 |
Not used for this test |
||||||||
LVDT_16 |
D16 |
N / A |
0.00500 in. |
194.000 |
N / A |
6.850 |
Placed on bottom side of Web | ||||||||
LVDT_17 |
D17 |
N / A |
- 0.00500 in. |
222.000 |
2.250 |
2.677 |
Measured from the Bottom Face of the Slab | ||||||||
LVDT_18 |
D18 |
N / A |
0.00500 in. |
222.000 |
22.500 |
4.803 |
Measured from the Bottom Face of the Slab | ||||||||
LVDT_19 |
D19 |
N / A |
- 0.00500 in. |
242.000 |
10.000 |
3.268 |
Measured from the Bottom Face of the Slab | ||||||||
LVDT_20 |
D20 |
N / A |
0.00500 in. |
242.000 |
22.000 |
2.480 |
Measured from the Bottom Face of the Slab | ||||||||
Ext. Str._1 |
ES1 |
N / A |
0.00150 in/in |
||||||||||||
Ext. Str._2 |
ES2 |
N / A |
0.00150 in/in |
||||||||||||
Ext. Str._3 |
ES3 |
N / A |
0.00150 in/in |
See Attached Figure for External |
|||||||||||
Ext. Str._4 |
ES4 |
N / A |
0.00150 in/in |
Strain Gage Locations |
|||||||||||
Ext. Str._5 |
ES5 |
N / A |
0.00150 in/in |
||||||||||||
Ext. Str._6 |
ES6 |
N / A |
0.00150 in/in |
||||||||||||
Ext. Str._7 |
ES7 |
N / A |
0.00150 in/in |
||||||||||||
Ext. Str._8 |
ES8 |
N / A |
0.00150 in/in |
||||||||||||
*** +X direction is defined as running north to south with north being 0. Measurements taken to the north face of the LVDT blocks. | |||||||||||||||
*** +Y direction is defined as running up to down with 0 being the bottom face of the slab, except where noted that measurement was taken from the top of the slab. Measurement was taken to the middle of the circular opening in the block. | |||||||||||||||
IMPORTANT NOTE: Sensor for D7 was not working. Sensor from D9 was placed in location of D7. | |||||||||||||||
Table 9. Instrumentation for HJ-4 Without FRP Repair
Hybrid Joist Test |
HJ-4 |
Date: June 3, 1996 |
|||||||||||
USA Construction Engineering Research Laboratories |
(First Test without FRP) |
||||||||||||
CERL |
CIR |
Conversion |
Location |
Location |
Gage |
||||||||
Instrument |
Name/ |
Name |
Factor |
(X - Dir.) |
(Y - Dir.) |
Length |
Comments |
||||||
Cable # |
(per volt) |
(in.) |
(in.) |
(in.) |
|||||||||
Cell_N |
N / A |
5.000 kips |
141.000 |
N / A |
N / A |
Concentrated Load - 50 Kip Actuator | |||||||
Stroke_N |
N / A |
0.300 inches |
141.000 |
N / A |
N / A |
||||||||
Cell_S |
N / A |
5.000 kips |
250.000 |
N / A |
N / A |
Concentrated Load - 50 Kip Actuator | |||||||
Stroke_S |
N / A |
0.300 inches |
250.000 |
N / A |
N / A |
||||||||
POT_N |
P1 |
N / A |
1.994 inches |
141.000 |
N / A |
N / A |
Third span Deflection - Potentiometer | ||||||
POT_Mid |
P2 |
N / A |
1.996 inches |
192.000 |
N / A |
N / A |
Midspan Deflection - Potentiometer | ||||||
POT_S |
P3 |
N / A |
2.000 inches |
278.000 |
N / A |
N / A |
Quarter span Deflection - Potentiometer | ||||||
Int_1 |
IS1 / 19 |
s19 |
0.00150 in/in |
40.000 |
N / A |
N / A |
Placed by the CIR |
||||||
Int_2 |
IS2 / 16 |
s20 |
0.00150 in/in |
40.000 |
N / A |
N / A |
Placed by the CIR |
||||||
Int_3 |
IS3 / 21 |
s21 |
0.00150 in/in |
40.000 |
N / A |
N / A |
Placed by the CIR |
||||||
Int_4 |
IS4 / 28 |
s28 |
0.00150 in/in |
141.000 |
N / A |
N / A |
Placed by the CIR |
||||||
Int_5 |
IS5 / 26 |
s26 |
0.00150 in/in |
119.000 |
N / A |
N / A |
Placed by the CIR |
||||||
Int_6 |
IS6 / 30 |
s30 |
0.00150 in/in |
141.000 |
N / A |
N / A |
Placed by the CIR |
||||||
Int_7 |
IS7 / 31 |
s31 |
0.00150 in/in |
163.000 |
N / A |
N / A |
Placed by the CIR |
||||||
Int_8 |
IS8 / 27 |
s27 |
0.00150 in/in |
119.000 |
N / A |
N / A |
Placed by the CIR |
||||||
Int_9 |
IS9 / 33 |
s33 |
0.00150 in/in |
163.000 |
N / A |
N / A |
Placed by the CIR |
||||||
Int_10 |
IS10 / 34 |
s34 |
0.00150 in/in |
192.000 |
N / A |
N / A |
Placed by the CIR |
||||||
Int_11 |
IS11 / 35 |
s35 |
0.00150 in/in |
192.000 |
N / A |
N / A |
Placed by the CIR |
||||||
Int_12 |
IS12 / 36 |
s36 |
0.00150 in/in |
192.000 |
N / A |
N / A |
Placed by the CIR |
||||||
LVDT_1 |
D1 |
N / A |
0.00494 in. |
72.750 |
1.000 |
7.205 |
Measured from the Top of the Slab | ||||||
LVDT_2 |
D2 |
N / A |
0.00497 in. |
71.375 |
3.000 |
6.063 |
Measured from the Bottom Face of the Slab | ||||||
LVDT_3 |
D3 |
N / A |
0.00495 in. |
69.125 |
12.250 |
2.913 |
Measured from the Bottom Face of the Slab | ||||||
LVDT_4 |
D4 |
N / A |
0.00497 in. |
145.125 |
1.000 |
5.748 |
Measured from the Top of the Slab | ||||||
LVDT_5 |
D5 |
N / A |
0.00496 in. |
143.375 |
3.500 |
5.197 |
Measured from the Bottom Face of the Slab | ||||||
LVDT_6 |
D6 |
N / A |
0.00496 in. |
143.375 |
11.000 |
2.559 |
Measured from the Bottom Face of the Slab | ||||||
LVDT_7 |
D7 |
N / A |
0.00496 in. |
142.375 |
22.750 |
5.236 |
Measured from the Bottom Face of the Slab | ||||||
LVDT_8 |
D8 |
N / A |
0.00495 in. |
168.125 |
1.000 |
5.236 |
Measured from the Top of the Slab | ||||||
LVDT_9 |
D9 |
N / A |
0.00496 in. |
167.375 |
3.000 |
2.441 |
Measured from the Bottom Face of the Slab | ||||||
LVDT_10 |
D10 |
N / A |
0.00499 in. |
168.375 |
22.750 |
2.441 |
Measured from the Bottom Face of the Slab | ||||||
LVDT_11 |
D11 |
N / A |
0.00489 in. |
195.000 |
1.000 |
6.417 |
Measured from the Top of the Slab | ||||||
LVDT_12 |
D12 |
N / A |
0.00496 in. |
193.875 |
3.000 |
7.283 |
Measured from the Bottom Face of the Slab | ||||||
LVDT_13 |
D13 |
N / A |
0.00496 in. |
195.500 |
22.500 |
5.197 |
Measured from the Bottom Face of the Slab | ||||||
LVDT_14 |
D14 |
N / A |
0.00491 in. |
194.750 |
N / A |
6.260 |
Placed on top of Slab |
||||||
LVDT_15 |
D15 |
N / A |
0.00496 in. |
N / A |
N / A |
N / A |
Not used for this test, Sensor moved to D13 | ||||||
LVDT_16 |
D16 |
N / A |
0.00500 in. |
195.250 |
N / A |
6.299 |
Placed on bottom side of Web |
||||||
LVDT_17 |
D17 |
N / A |
-0.00503 in. |
220.000 |
2.250 |
7.638 |
Measured from the Bottom Face of the Slab | ||||||
LVDT_18 |
D18 |
N / A |
0.00487 inches |
220.375 |
22.500 |
4.055 |
Measured from the Bottom Face of the Slab | ||||||
LVDT_19 |
D19 |
N / A |
-0.00501 in. |
244.000 |
10.000 |
2.362 |
Measured from the Bottom Face of the Slab | ||||||
LVDT_20 |
D20 |
N / A |
0.00500 in. |
244.125 |
22.000 |
2.717 |
Measured from the Bottom Face of the Slab | ||||||
*** +X direction is defined as running north to south with north being 0. Measurements taken to the north face of the LVDT blocks. | |||||||||||||
*** +Y direction is defined as running up to down with 0 being the bottom face of the slab, except where noted that measurement was taken from the top of the slab. Measurement was taken to the middle of the circular opening in the block. | |||||||||||||
IMPORTANT NOTES: Sensor for D15 was moved into the D13 position. D15 position was not used. | |||||||||||||
Table 10. Instrumentation for HJ-4 With FRP Repair
Hybrid Joist Test |
HJ-4 |
(2nd Test with FRP) |
|||||||
USA Construction Engineering Research Laboratories |
|||||||||
Champaign, IL |
|||||||||
Date: |
August 2 1996 |
||||||||
CERL |
CIR |
Conversion |
Location |
Location |
Gage |
||||
Instrument |
Name |
Name |
Factor |
(X - Dir.) |
(Y - Dir.) |
Length |
Comments |
||
/ Cable # |
(per volt) |
(in.) |
(in.) |
(in.) |
|||||
Cell_N |
N / A |
5.000 kips |
141.000 |
N / A |
N / A |
Concentrated Load - 50 Kip Actuator | |||
Stroke_N |
N / A |
0.300 inches |
141.000 |
N / A |
N / A |
||||
Cell_S |
N / A |
5.000 kips |
250.000 |
N / A |
N / A |
Concentrated Load - 50 Kip Actuator | |||
Stroke_S |
N / A |
0.300 inches |
250.000 |
N / A |
N / A |
||||
POT_N |
P1 |
N / A |
2.000 inches |
141.000 |
N / A |
N / A |
Third span Deflection - Potentiometer | ||
POT_Mid |
P2 |
N / A |
2.000 inches |
192.000 |
N / A |
N / A |
Midspan Deflection - Potentiometer | ||
POT_S |
P3 |
N / A |
2.000 inches |
278.000 |
N / A |
N / A |
Quarter span Deflection - Potentiometer | ||
Int_1 |
IS1 / 19 |
s19 |
0.00150 in/in |
40.000 |
N / A |
N / A |
Placed by the CIR |
||
Int_2 |
IS2 / 16 |
s20 |
0.00150 in/in |
40.000 |
N / A |
N / A |
Placed by the CIR |
||
Int_3 |
IS3 / 21 |
s21 |
0.00150 in/in |
40.000 |
N / A |
N / A |
Placed by the CIR |
||
Int_4 |
IS4 / 28 |
s28 |
0.00150 in/in |
141.000 |
N / A |
N / A |
Placed by the CIR |
||
Int_5 |
IS5 / 26 |
s26 |
0.00150 in/in |
119.000 |
N / A |
N / A |
Placed by the CIR |
||
Int_6 |
IS6 / 30 |
s30 |
0.00150 in/in |
141.000 |
N / A |
N / A |
Placed by the CIR |
||
Int_7 |
IS7 / 31 |
s31 |
0.00150 in/in |
163.000 |
N / A |
N / A |
Placed by the CIR |
||
Int_8 |
IS8 / 27 |
s27 |
0.00150 in/in |
119.000 |
N / A |
N / A |
Placed by the CIR |
||
Int_9 |
IS9 / 33 |
s33 |
0.00150 in/in |
163.000 |
N / A |
N / A |
Placed by the CIR |
||
Int_10 |
IS10 / 34 |
s34 |
0.00150 in/in |
192.000 |
N / A |
N / A |
Placed by the CIR |
||
Int_11 |
IS11 / 35 |
s35 |
0.00150 in/in |
192.000 |
N / A |
N / A |
Placed by the CIR |
||
Int_12 |
IS12 / 36 |
s36 |
0.00150 in/in |
192.000 |
N / A |
N / A |
Placed by the CIR |
||
LVDT_1 |
D1 |
N / A |
0.00500 inches |
72.750 |
1.000 |
7.205 |
Measured from the Top of the Slab | ||
LVDT_2 |
D2 |
N / A |
0.00500 inches |
69.000 |
3.000 |
6.000 |
Measured from the Bottom Face of the Slab | ||
LVDT_3 |
D3 |
N / A |
0.00500 inches |
68.500 |
12.000 |
3.125 |
Measured from the Bottom Face of the Slab | ||
LVDT_4 |
D4 |
N / A |
0.00500 inches |
145.125 |
1.000 |
5.748 |
Measured from the Top of the Slab | ||
LVDT_5 |
D5 |
N / A |
0.00500 inches |
143.375 |
3.500 |
5.197 |
Measured from the Bottom Face of the Slab | ||
LVDT_6 |
D6 |
N / A |
0.00500 inches |
143.375 |
11.000 |
2.559 |
Measured from the Bottom Face of the Slab | ||
LVDT_7 |
D7 |
N / A |
0.00500 inches |
142.375 |
22.750 |
5.236 |
Measured from the Bottom Face of the Slab | ||
LVDT_8 |
D8 |
N / A |
0.00500 inches |
168.125 |
1.000 |
5.236 |
Measured from the Top of the Slab | ||
LVDT_9 |
D9 |
N / A |
N / A |
N / A |
N / A |
N / A |
Not used for this test, Sensor moved to D5 | ||
LVDT_10 |
D10 |
N / A |
0.00500 inches |
168.375 |
22.750 |
2.441 |
Measured from the Bottom Face of the Slab | ||
LVDT_11 |
D11 |
N / A |
0.00500 inches |
195.000 |
1.000 |
6.417 |
Measured from the Top of the Slab | ||
LVDT_12 |
D12 |
N / A |
0.00500 inches |
193.875 |
3.000 |
7.283 |
Measured from the Bottom Face of the Slab | ||
LVDT_13 |
D13 |
N / A |
0.00500 inches |
195.500 |
22.500 |
5.197 |
Measured from the Bottom Face of the Slab | ||
LVDT_14 |
D14 |
N / A |
0.00500 inches |
194.750 |
N / A |
6.260 |
Placed on top of Slab |
||
LVDT_15 |
D15 |
N / A |
N / A |
N / A |
N / A |
N / A |
Not used for this test, Sensor moved to D13 | ||
LVDT_16 |
D16 |
N / A |
0.00500 inches |
195.250 |
N / A |
6.299 |
Placed on bottom side of Web |
||
LVDT_17 |
D17 |
N / A |
- 0.00500 in. |
220.000 |
2.250 |
7.638 |
Measured from the Bottom Face of the Slab | ||
LVDT_18 |
D18 |
N / A |
0.00500 inches |
220.375 |
22.500 |
4.055 |
Measured from the Bottom Face of the Slab | ||
LVDT_19 |
D19 |
N / A |
- 0.00500 in. |
244.000 |
10.000 |
2.362 |
Measured from the Bottom Face of the Slab | ||
LVDT_20 |
D20 |
N / A |
0.00500 inches |
244.125 |
22.000 |
2.717 |
Measured from the Bottom Face of the Slab | ||
Ext. Str._1 |
ES1 |
N / A |
0.00150 in / in |
||||||
Ext. Str._2 |
ES2 |
N / A |
0.00150 in / in |
||||||
Ext. Str._3 |
ES3 |
N / A |
0.00150 in / in |
See Attached Figure for External Strain Gage Locations |
|||||
Ext. Str._4 |
ES4 |
N / A |
0.00150 in / in |
||||||
Ext. Str._5 |
ES5 |
N / A |
0.00150 in / in |
||||||
Ext. Str._6 |
ES6 |
N / A |
0.00150 in / in |
||||||
Ext. Str._7 |
ES7 |
N / A |
0.00150 in / in |
||||||
Ext. Str._8 |
ES8 |
N / A |
0.00150 in / in |
||||||
*** +X direction is defined as running north to south with north being 0. Measurements taken to the north face of the LVDT blocks. | |||||||||
*** +Y direction is defined as running up to down with 0 being the bottom face of the slab, except where noted that measurement was taken from the top of the slab. Measurement was taken to the middle of the circular opening in the block. | |||||||||
IMPORTANT NOTES: |
|||||||||
Sensor for D15 was moved into the D13 position. D15 position was not used. | |||||||||
Sensor for D9 was moved into the D5 position. D9 position was not used. | |||||||||
Table 11. Principal Experimental Test Results for Hybrid Joists
Joist designation |
Experimental cracking load*
|
First Crack Location |
Applied
|
Total Failure Load
|
Equivalent Uniform Load
|
Type of failure |
HJ-3 |
midspan,
|
52.0 |
53.0 |
0.62 |
shear | |
HJ-4 |
midspan,
|
56.6 |
56.6** |
0.67 |
no failure | |
HJ-6 |
11.7 |
midspan, bottom chord |
48.0 |
49.0 |
0.57 |
shear |
HJ-7 |
31.5 |
midspan
|
64.0 |
65.0 |
0.76 |
flexure |
* Sum of two actuators.
**No failure occurred.
Table 12. Camber and Deflection for Hybrid Joists (in.)
Joist designation |
Camber at release |
LL Deflection |
SIDL + LL Deflection |
Deflection at peak load |
Deflection at failure |
HJ-3 |
0.40 |
.09 |
.14 |
5.66 |
12.58 |
HJ-4 without FRP |
0.45 |
.10 |
.16 |
7.66 |
7.67* |
HJ-4 with FRP repair |
NA |
.10 |
.16 |
8.62 |
10.06* |
HJ-6 |
0.45 |
0.03 |
0.16 |
3.52 |
3.52 |
HJ-7 |
0.38 |
0.02 |
0.14 |
16.6 |
16.6 |
* Deflection at end of test; no failure occurred.
CERL DISTRIBUTION
Chief of Engineers
ATTN: CEHEC-IM-LH (2)
ATTN: CEHEC-IM-LP (2)
ATTN: CECW
ATTN: CECW-O
ATTN: CECW-P
ATTN: CECW-PR
ATTN: CEMP-CE
ATTN: CERD-L
ACS(IM) 22060
ATTN: DAIM-FDP
CEISC 22310-3862
ATTN: CEISC-E
ATTN: CEISC-FT
ATTN: CEISC-ZC
US Army Engr District
ATTN: Library (40)
US Army Engr Division
ATTN: Library (8)
US Army Engineering and Support Center
ATTN: CEHND 35807-4301
Naval Facilities Engr Command
ATTN: Facilities Engr Command (8)
ATTN: Engrg Field Divisions (10)
ATTN: Engrg Field Activities (4)
ATTN: Public Works Center (8)
ATTN: Naval Constr Battalion Ctr 93043
ATTN: Naval Facil Engr Service Ctr 93043-4328
Tyndall AFB 32403
ATTN: HQAFCESA/CES
ATTN: Engrg & Srvc Lab
American Public Works Assoc. 64104-1806
US Gov't Printing Office 20401
ATTN: Rec Sec/Deposit Sec (2)
Defense Tech Info Center 22060-6218
ATTN: DTIC-O (2)
103
3/98